<Figure 1> is read setting example of SEC Standard UPS controller.
		![]()  | 
	
| <Figure 1> Read setting example of SEC Standard UPS | 
Device part of <Figure 1> input Com Port(COM1), Com Baud(19200), Parity Bit(0), Data Bit(8), Stop Bit(1) respectively, according to controller. (In case of using Ethernet, input Connection Type(TCP/IP), IP address of PLC(192.168.1.70), TCP service port(6001), respectively)
Also, you can input whether to use CRC(0 = Not use, 1 = Use, Default : 0) of protocol as 0 or 1, Option part.
But, in case of setting as CRC use(1), send the AP0 command first, before communication.
SEC Standard UPS communication driver's read schedule
| READ | STATION (Not use)  | 
    Read Command | Read Start Address (Not use)  | 
    Save Start Address for Communication Server | Read Size (Fixed by each command)  | 
  
| FLOAT, | 0, | ST1, | 0, | 0, | 1, | 
| FLOAT, | 0, | ST2, | 0, | 10, | 1, | 
| FLOAT, | 0, | ST3, | 0, | 30, | 1, | 
| FLOAT, | 0, | ST4, | 0, | 50, | 1, | 
| FLOAT, | 0, | ST5, | 0, | 70, | 1, | 
1) STATION : Don't care.
2) Read Command : Select among AP1, AP2, ATR, MAN, MOD, NOM, SDA, ST1 ~ ST5, STR, UID and VER.
3) Read Start Address : Don't care.
4) Save Start Address for Communication Server : Buf position to save status value which have been read.
5) Read Size : The number of item to read at a time. Fixed according to each read command(Refer to Table 1 ~ Table 16).
| Total Read Size | Contents | Contents | 
| Max 46 | Available parameter 1 | Available parameter number 1 ~ 46 | 
| <Table 1> Read size and data contents of AP1 read command | ||
| Total Read Size | Contents | Contents | 
| Max 43 | Available parameter 2 | Available parameter number 47 ~ 89 | 
| <Table 2> Read size and data contents of AP2 read command | ||
| Total Read Size | Contents | Max Data Length | Unit | 
| 1 | Auto Reboot | 1 | Int 1 =
      ON(auto),     2 – OFF(manual)  | 
  
| <Table 3> Read size and data contents of ATR read command | |||
| Total Read Size | Contents | Max Data Length | Unit | Remarks | 
| 1 | Manufacturer | 32 | Letter | Impossible to transfer to communication memory, because of String | 
| <Table 4> Read size and data contents of MAN read command | ||||
| Total Read Size | Contents | Max Data Length | Unit | Remarks | 
| 1 | Model | 64 | Letter | Impossible to transfer to communication memory, because of String | 
| <Table 5> Read size and data contents of MOD read command | ||||
| Total Read Size | Contents | Max Data Length | Unit | Remarks  | 
  
| 12 | Nominal Input Voltage | 3 | Volt | V  | 
  
| Nominal Input Frequency | 3 | HZ | 0.1 HZ  | 
  |
| Nominal Output Voltage | 3 | Volt | V  | 
  |
| Nominal Output Frequency | 3 | HZ | 0.1 HZ  | 
  |
| Nominal VA Rating | 5 | VA | Volts-amps  | 
  |
| Nominal Output Electricity | 5 | W | 
          | 
  |
| Low Battery Time | 2 | Min | Minutes  | 
  |
| Audiable Alarm | 1 | 1 : disabled 2 : enabled 3 : muted 4 : disabled until low battery  | 
  ||
| Low Voltage Transfer Point | 3 | Volt | V  | 
  |
| High Voltage Transfer Point | 3 | Volt | V  | 
  |
| Battery Installed Date | 8 | Month/Day/Year  | 
  ||
| Nominal
       | 
    5 | Day | days  | 
  |
| <Table 6> Read size and data contents of NOM read command | ||||
| Total Read Size | Contents | Max Data Length | Unit | 
| 1 | Shutdown type | 1 | Int 1 = UPS output, 2 = UPS system  | 
  
| <Table 7> Read size and data contents of SDA read command | |||
| Total Read Size | Contents | Max Data Length | Unit | Remarks  | 
  
| 8 | 
       | 
    1 | 0 : Good 1 : Weak 2 : Replace  | 
  |
| 
       | 
    1 | 0 : Ok 1 : Low 2 : Depleted  | 
  ||
| 
       | 
    1 | 0 : Floating 1 : Charging 2 : Resting 3 : Discharging  | 
  ||
| Seconds on
       | 
    5 | Sec | Seconds  | 
  |
| Estimated Minutes | 3 | Min | Minutes  | 
  |
| Estimated Charge | 3 | % | Percent  | 
  |
| 
       | 
    4 | V | 0.1 V  | 
  |
| 
       | 
    4 | A | 0.1 A  | 
  |
| <Table 8> Read size and data contents of ST1 read command | ||||
| Total Read Size | Contents  | 
    Max Data Length | Unit | Remarks  | 
  
| 14 | Input Line Bads  | 
    3 | Int  | 
  |
Input Num Lines  | 
    1 | Int (1 ~ 3)  | 
  ||
Input Frequency 1  | 
    3 | HZ | 0.1 HZ  | 
  |
Input Voltage 1  | 
    4 | V | 0.1 V  | 
  |
Input Current 1  | 
    4 | A | 0.1 A  | 
  |
Input Electricity 1  | 
    5 | W | 
          | 
  |
Input Frequency 2  | 
    3 | HZ | 0.1 HZ  | 
  |
Input Voltage 2  | 
    4 | V | 0.1 V  | 
  |
Input Current 2  | 
    4 | A | 0.1 A  | 
  |
Input Electricity 2  | 
    5 | W | 
          | 
  |
Input Frequency 3  | 
    3 | HZ | 0.1 HZ  | 
  |
Input Voltage 3  | 
    4 | V | 0.1 V  | 
  |
Input Current 3  | 
    4 | A | 0.1 A  | 
  |
Input Electricity 3  | 
    5 | W | 
          | 
  |
| 
 <Table 9> Read size and data contents of ST2 read command  | 
  ||||
| Total Read Size | Contents  | 
    Max Data Length | Unit | Remarks  | 
  
14  | 
    Output Frequency  | 
    3 | HZ | 0.1 HZ  | 
  
Output Num Lines  | 
    1 | Int (1 ~ 3)  | 
  ||
Output Voltage 1  | 
    4 | V | 0.1 V  | 
  |
Output Current 1  | 
    4 | A | 0.1 A  | 
  |
Output Electricity 1  | 
    5 | W | 
          | 
  |
Output Load 1  | 
    3 | % | Percent  | 
  |
Output Voltage 2  | 
    4 | V | 0.1 V  | 
  |
Output Current 2  | 
    4 | A | 0.1 A  | 
  |
Output Electricity 2  | 
    5 | W | 
          | 
  |
Output Load 2  | 
    3 | % | Percent  | 
  |
Output Voltage 3  | 
    4 | V | 0.1 V  | 
  |
Output Current 3  | 
    4 | A | 0.1 A  | 
  |
Output Electricity 3  | 
    5 | W | 
          | 
  |
Output Load 3  | 
    3 | % | Percent  | 
  |
| <Table 10> Read size and data contents of ST3 read command | ||||
| Total Read Size | Contents  | 
    Max Data Length | Unit | Remarks  | 
  
11  | 
    Bypass Frequency  | 
    3 | HZ | 0.1 HZ  | 
  
Bypass Num Lines  | 
    1 | Int (1 ~ 3)  | 
  ||
Bypass Voltage 1  | 
    4 | V | 0.1 V  | 
  |
Bypass Current 1  | 
    4 | A | 0.1 A  | 
  |
Bypass Electricity 1  | 
    5 | W | 
          | 
  |
Bypass Voltage 2  | 
    4 | V | 0.1 V  | 
  |
Bypass Current 2  | 
    4 | A | 0.1 A  | 
  |
Bypass Electricity 2  | 
    5 | W | 
          | 
  |
Bypass Voltage 3  | 
    4 | V | 0.1 V  | 
  |
Bypass Current 3  | 
    4 | A | 0.1 A  | 
  |
Bypass Electricity 3  | 
    5 | W | 
          | 
  |
| <Table 11> Read size and data contents of ST4 read command | ||||
| Total Read Size | Contents | Max Data Length | Remarks | 
| 15 | Temp Alarm | 1 | 0 : No Alarm1 : Alarm | 
| Input Bad Alarm | 1 | ||
| Output Bad Alarm | 1 | ||
| Overload Alarm | 1 | ||
| Bypass Bad Alarm | 1 | ||
| Output Off Alarm | 1 | ||
| UPS Shutdown Alarm | 1 | ||
| Charger Failure Alarm | 1 | ||
| System Off Alarm | 1 | ||
| Fan Failure Alarm | 1 | ||
| Fuse Failure Alarm | 1 | ||
| General Failure Alarm | 1 | ||
| Awaiting Power Alarm | 1 | ||
| Shutdown Pending Alarm | 1 | ||
| Shutdown Imminent Alarm | 1 | ||
| <Table 12> Read size and data contents of ST5 read command | |||
| Total Read Size | Contents | Max Data Length | Remarks  | 
  
| 2 | Test Result Summary | 1 | 0 : No Test 1 : Test Passed 2 : Test in Progress 3 : General Test Failed 4 :
         5 : Deep Test Failed  | 
  
| Test Result Detail | 64 | Impossible to transfer to communication memory, because of String | |
| <Table 13> Read size and data contents of STR read command | |||
| Total Read Size | Contents | Max Data Length | Remarks | 
| 1 | UPS Baud Rate | 5 | 1200, 2400, 4800, 9600, 19200 | 
| <Table 14> Read size and data contents of UBR read command | |||
| Total Read Size | Contents | Max Data Length | Unit | Remarks | 
| 1 | UPS Indentification | 64 | Letter | Impossible to transfer to communication memory, because of String | 
| <Table 15> Read size and data contents of UID read command | ||||
| Total Read Size | Contents | Max Data Length | Unit | Remarks | 
| 1 | Software Version | 32 | Letter | Impossible to transfer to communication memory, because of String | 
| <Table 16> Read size and data contents of VER read command | ||||
Digital Write
You can change the status value of SEC Standard UPS by using digital write.
Digital write setting parameters are as follows :
PORT Connected PORT number 0 ~ 255
STATION Don't care
ADDRESS Don't care
EXTRA1 Setting command ATR (Auto Reboot : Refer to <Table 3>),
NOM(Refer to <Table 5> – Write output data to NOM_DATA.???(??? = port no) in SCAN Server Directory of Work Directory, such as in order of <Table 5>),
PSD(Shutdown action : -1 – abort, 0 – immediate, 1 >= - seconds until shutdown),
RWD(Shutdown type : seconds), SDA(Refer to <Table 7>),
STD(Startup after delay : -1 – abort, 0 – immediate, 1 >= - seconds until startup),
TST(Test : -1 – Abort Test, 0 – No Effect, 1 – General Test, 2 – Battery Test, 3 – Deep Test),
UBR(UPS Baud Rate : 1200, 2400, 4800, 9600, 19200),
UID(Sets UPS ID String : Max 64 letters, Write UPS ID to UID_DATA.??? (??? = port no) in SCAN Server Directory of Work Directory),
CN1 (Rectifier ON/OFF : 1 = ON, 0 = OFF),
CN2 (Inverter ON/OFF : 1 = ON, 0 = OFF),
CN3 (Static ON/OFF : 1 = ON, 0 = OFF),
AP0 (Command for using CRC check : 1 = In case of AP0 command, CRC is included, 0 = In case of AP0 command, CRC isn't included),
EXTRA2 Don't care
Write example 1)
Port : 0, Extra1 : ATR
If you set as above and write digital value, you can change(ON/OFF) Auto Reboot status value of SEC Standard UPS.
Analog Write
Analog write and digital write have the same settings, but output value is only different.
<Figure 2> is the front of appearance for SEC UPS device.
 ![]()  | 
	
| <Figure 2> Example of appearance in front of SEC UPS device |